- Condensation monitors and dew point sensors for HVAC
Condensation monitors and dew point sensors for HVAC
Moisture can form on chilled ceilings and chilled-water pipes when the surface temperature reaches the dew point of the surrounding air. At S+S we offer HYGRASREG® condensation and dew point monitors and HYGRASGARD® models with Modbus RTU. Start with the mounting location and the response your system needs. Choose from models with a switching contact, an analogue output or Modbus RTU. Check whether an integrated or remote sensing element suits your measurement point.
What do condensation monitors and dew point sensors do?
Condensation monitors and dew point sensors detect conditions under which moisture can form on a cold surface. For chilled ceilings, chilled-water pipes and other cooled surfaces, S+S offers models with switching contacts, analogue outputs or Modbus RTU. Select the device by measurement location and the response required from the controls.
When can condensation form on a chilled ceiling or pipe?
As air next to a surface cools, its relative humidity can rise. Condensation may form when the surface reaches or falls below the surrounding air’s dew point. The critical point depends on local humidity, surface temperature and the installation.
For illustration, air at 24 °C and 60% relative humidity has a dew point of about 15.8 °C. An uninsulated surface below that temperature is at risk under those conditions. Use the project requirements and selected device instructions to determine switching thresholds, safety margins and restart behaviour.
Condensation, dew point or leak detection?
Condensation monitor for a local signal. Place the sensing element at the point where condensation is likely. A model with a changeover contact provides a switching state to the controller. For example, a chilled ceiling circuit might need a dedicated signal from its most critical point.
Dew point monitoring with readings. Depending on the device and interface, continuous humidity readings or calculated values are available. To log dew point temperature in °C, confirm that the interface provides that quantity. The TW-U/W analogue output represents relative humidity. The TW-Modbus-T3 can provide calculated dew point temperature over Modbus. TW-U/W specifications · TW-Modbus-T3 specifications
Leak detection for escaping water. Use a leak sensor where escaping or accumulated water needs to be detected, such as in a collection area. A project can use both types of device at different locations for different tasks. S+S leak sensors
Choose a monitor for the measurement point and BMS
-
Local changeover contact · HYGRASREG® KW-W-SD
For ceilings, pipes or cooled surfaces suitable for mounting the sensor as specified in the instructions. This variant has an integrated sensing element and a changeover contact. Consult the documentation for switching behaviour and permitted operating conditions.
Remote sensing element · HYGRASREG® KW-W-external
Useful where the measurement point has limited space or the housing needs to remain accessible elsewhere. The sensing element mounts separately. Consider the lead, mounting accessories and access when planning the installation.
Analogue and switching outputs · HYGRASREG® TW-U/W
For controls that need a continuous humidity value as well as a switching state. This variant provides a 0–10 V output for relative humidity and a separate switching output. Specify them as separate BMS data points.
Read dew point temperature digitally · HYGRASGARD® TW-Modbus-T3
For projects that process multiple values over Modbus RTU. Consult the documentation for values such as relative humidity and calculated dew point temperature. Specify the points that the controller needs before commissioning.
Chilled ceilings, chilled-water pipes and remote points
Chilled ceilings. Select a point representative of condensation risk, considering cooling distribution and mounting conditions. A slightly cooled area may not represent a colder section. Coordinate the location with system design and mount the sensing element as specified for the selected model.
Chilled-water pipes. Check where the element will sit on the pipe or monitored surface. Account for insulation, fastening and service access. A remote element can monitor the required spot while the housing stays accessible. Coordinate the insulation and the sensor mounting.
Remote sensing points. Record the sensor and housing locations separately. This helps the commissioning team match the device to the right circuit and find the connections later. Confirm the enclosure rating, probe design and permitted conditions at both positions.
Check alarms, controls and restart behaviour
Define the response to a signal. Depending on the control sequence, the BMS might display an alarm, limit a cooling circuit or operate a valve. Use the project requirements to determine when cooling can resume. Document the response to loss of signal and how each alarm is assigned to a zone.
Use a consistent circuit name, such as floor, zone and circuit number. Assign responsibility for checking the measurement point after refurbishment. Moving a sensor to another surface can expose it to different conditions even if the device is the same.
During commissioning, check the signal from sensor to controller. For a contact, verify its expected state and state change against the instructions. For 0–10 V, check the scale and the transmitted quantity. For Modbus RTU, check the register, unit and fault behaviour. Include the alarm display and agreed plant response in the functional test.
Worked application with a local contact and an additional trend value
In a building with several chilled ceiling circuits, each monitored circuit needs an identifiable condensation signal. A model with a changeover contact can provide a local signal at an accessible critical point. The controller assigns it to the correct circuit. Where space is tight, check whether a remote sensing element fits.
For a trend in the BMS, specify whether the operator needs relative humidity or calculated dew point temperature. That choice affects the model and interface. Record the location, quantity, unit and expected system response in the point schedule. After replacement, verify that the new variant provides the same output quantity and assignment.
Choose the right monitor for your project
Start with the measurement point and the required controls response. Compare sensing element design, enclosure rating and output. The specifications list measured values, electrical ratings and mounting requirements.
Frequently asked questions
Does a condensation monitor signal visible water?
A model signals the condition defined in its datasheet. Products differ in sensing method and switching behaviour. Choose the device for the specified task and confirm its switching point. A purpose-built leak sensor is appropriate for detecting water that has escaped or pooled.
Does a 0–10 V output always represent dew point temperature?
The output quantity depends on the model. For example, the TW-U/W analogue output represents relative humidity. If the BMS needs dew point in °C, choose a device whose documentation explicitly lists that reading on the intended interface.
Where should the sensor sit on a chilled-water pipe?
Place it at a representative point where condensation risk is to be monitored. Follow the device instructions and site design. On insulated pipes, agree on the fixation and location during planning so the point remains accessible and identifiable.
When do I need a remote sensing element?
A remote element is useful if the housing will not fit at the measurement point or should remain accessible elsewhere. Check the lead length and routing, mounting hardware and permitted operating conditions for the selected variant.
Can dew point monitoring be integrated over Modbus RTU?
Yes, if the selected device reports the requested dew point reading and the controller supports the interface. The TW-Modbus-T3 provides calculated values over Modbus. Confirm the register and specify how the BMS handles thresholds, alarms and restart.
We also manufacture individually
Do you have special requirements? As a manufacturer with our own production facilities in Germany, we are also able to produce products outside of the standard range at any time.
Contact us
Secure payment methods
Do you have a question? We are at your disposal:
+49 911 519 470Mo. - Fr. 7.00am - 5.00pm CEST
- Choosing a selection results in a full page refresh.
- Opens in a new window.